Data logger for current 0-20mA, voltage 0-5V and binary signal Suhu dan kelembaban ( sensor, sistem monitoring online, instrument) Terlengkap
Data logger for current 0-20mA,
voltage 0-5V and binary signal
Data loggers are designed for record of voltage signal 0-5V (optionally 0-10V) or current signal 0-20mA. At the same time state of binary signal can be recorded. Values are stored to a non volatile electronic memory. Data transfer to the personal computer for further analysis is performed via USB, RS232, GSM or Ethernet interface by means of a proper adapter.
Main applications of data logger:
* Distant places with no electric power
* Long term field measurement
* Research and development
* Laboratories
* Technological processes
Advantages of data logger:
* included traceable calibration certificate from the manufacturer - Comet
* fast data transfer to the PC (full memory for approximately 30s)
* variability of connection to the computer - USB, RS232, Ethernet, GSM modem
* permanent connection to the PC enabled, data is possible to download even during logging
* large data memory 32000 values
* large dual line display with special symbols, switchable
* optional display of minimum and maximum measured values (reset of min/max memory from PC or by magnet)
* dual level alarm is enabled for each channel, alarm is indicated by blinking of the value on the LCD display
* two alarm modes are enabled: instant or with memory (detected alarm is indicated permanently till alarm memory is cleared)
* robust watertight case
* easy installation, locking enabled
* low power consumption from battery, battery life up to 6 years
* indication of remaining battery life, easy replacement of the battery
* logging start/stop is enabled: at certain time and date programmed from computer, by external binary signal or by delivered magnet
* also special logging mode is enabled, when logging runs only, if some of measured values are out of adjusted alarm limits
* input signal is recalculated and displayed in real measured physical units by means of the PC software
* each logger is possible to describe with text of maximum 32 characters
* each channel is possible to describe with text of maximum 16 characters
* password protection is enabled to prevent unauthorized manipulation with logger
TECHNICAL PARAMETERS
Measurement accuracy: ±0.2% FS
Resolution of voltage input: 13 bits (8192 levels)
Resolution of current input: 7900 levels
Signal character at binary input: from potential-less contact or two-state voltage signal
Minimum pulse duration at binary input: 500 ms (shorter pulses may not be recorded)
Maximum frequency at binary input: 0.5 Hz (i.e. maximum 5 pulses for 10 s)
Power current through contact at binary input: 3 uA (contact closed)
Voltage accross open contact at binary input: maximum 3.6 V
Low voltage level at binary input: 0 to +0.2 V (maximum current from the input 3 uA
High voltage level at binary input: +3.0 to +30 V (maximum current to the input 100 nA
Data logging interval: adjustable from 10s to 24hours
Display refresh and alarm state refresh: every 10 s
Total memory capacity: 32000 values (in non cyclic mode)
Data logging modes: noncyclic – logging stops after filling the memory
cyclic – after filling memory oldest data is overwritten by new
Operation temperature range: -30 to +70°C
Real time clock: year, leap year, month, day, hour, minute, second
Built-in connector for input signals: Canon 9 pins, male
Dimensions without connectors: 93x64x29mm
Weight including battery: 130g
Power: Lithium battery 3,6V, size AA
Typical battery life in operation from -5 to +35°C:
(if often operated outside of the above temperature range battery life can be reduced to 75%) 6 years
Battery life in continuous on-line mode with interval 1 minute: 4 years
Battery life in continuous on-line mode with interval 10 seconds: 1 year
Protection: IP67 - protected against influence of temporary immersion into water
Warranty: 2 years